額定额定值0.6/1kV塑料绝缘铜带屏蔽电力电缆
Plastic insulated copper tape screen power cables
with rated voltages 0.6/1kV
🍌本服务适宜于电机额定功率电压值0.6/1kV及下例输供配电新线路,具有着抗雷暴、抗电磁振动器扰乱和匀衡电极电位等功用,很广采采用领导层房屋建筑、火箭弹发场和紧密电子设备安全装置多的在日常生活中。
This product is applicable to being fixedly laid on the transmission and distribution line of rated voltage up to 0.6/1.0Kv with the use for power transmission. This product can be used in high-rise building, guided missile lanching site, the place where there are plenty of precise electronic equipments.🦩本成品具优厚的电器设备特性、抗遭雷击、抗磁感应干拢和匀衡电极电位耐高温特性,利于使用和保养,敷设时不受到起伏被限。
The product has good performance on electrical characteristic, light-stroke protection, resistance to electromangetic interference, equilibrium voltage, heat resistant.The product characteristic is easy installation and maintaince, especially there is no limit of head drop during the cable laying.GB/T 12706.1-2002 稳定相电压1 kV(Um=1.2 kV)到35 kV(Um=40.5 kV)挤包绝缘电力电缆及附件
第1部件:功率线电压 1kV(Um=1.2 kV)和3 kV(Um=3.6 kV)电揽
💃Power cables with extruded insulation and their for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3 kV(Um=3.6 kV)
ꦿIEC 60502-1:1997 特殊的电压1 kV(Um=1.2 kV)到30 kV(Um=36 kV)挤包接地电量电线及附属品
第2组成部分:额定负载交流电压 1 kV(Um=1.2kV)和3 kV(Um=3.6kV)电览
🦩Power cables with extruded insulation and their for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3 kV(Um=3.6 kV)
Q/12BJ4973-2002 功率电流0.6/1kV 五芯pp塑料绝缘电阻用电低压电缆
Q/12BJ4973-2002 Five cores extruded plastic insulated power cables with rated voltages 0.6/1Kv🍌Q/12BJ 5142-2003 电机额定功率电流值0.6/1kVPVC电绝缘铝合金禁掉电网电线
Q/12BJ 5142-2003 Plastic insulated copper tape screen power cables with rated voltages 0.6/1kVGB/T 3956-1997 低压电缆的导体
GB/T 3956-1997 Conductor of Cables缆线特殊电流电压U0/U(Um)为:0.6/1(1.2)kV
Rated Voltage of cable U0/U(Um)::0.6/1(1.2)kV
这里面:Notes
U0:拖链电缆制作用的导体对地或黑色金属拦截两者之间的额定容量工频电阻;
Rated A.C. Voltage between conductor and ground/metal screen;U:电揽设汁用的导体间的额定的工频电压值;
Rated A.C. Voltage between conductorsUm:产品可能承受的“高系统的直流电压“的最大化值。
The maximum system voltage which the equipments can be beared🅘高压低压电览的额定值相电压应合适高压低压电览隶属系統化的程序运行环境。为了让更加方便的选择高压低压电览,将系統化定义为下面三种:
The rated voltage of cable shall be applicable to system operation condition where the cable lain in. According to cable selecting, the system will be described as 3 types as follow:——A类:某个相导体与地或等电位连接导体交往时,能在1min内与系统性隔绝。
When any phase of cable conductor is contacting with earth conductor, the cable will be isolated with the system.𒊎——B类:可在单相电一定接地洛天依时作瞬时运作,但不管什么情況下不应该超越8h,年年接地保护错误码总不断事件不应该超越125h。
The system is allowed to run for 8 hours, when the single-phase earth fault is existing. And the total earth-fault time of 1 year won't be above 125 hours.——C类:包涵不归于A类和B类的系统化。
They are including all systems besides A and B.🎉注:在模式化保护保护接地故障率率问题不是当即电脑自动关闭时,故障率率问题时间加在电线绝缘层演了高的电场比强度比强度,会在特定情况上减少电线质保期。如模式化实际会三天两头地作业在长久的保护保护接地故障率率问题的状态下,该模式化应划为C类。
When the system earth fault can't be removed automatically, the life of cable will be shortened in some degree because of the over-high electric stess beared by cable insulation.
用做三项评分系統的线缆,U0的强烈推荐值见表1。
The recommended figure of U0 ✨see the book 1, which are suitalbe for the three systems.
表1 额定容量电阻值U0推建值
Table1 The recommended figure of U0
程序极高电压电流Um/ kVThe maximum system voltage | 额定负载电阻/Kv Rated Voltage/ kV | |
A类、B类 System categories A and B | C类 Systems categories C | |
1.2 | 0.6 | 0.6 |
💎2、 导体额定的作业温湿度The rated temperature of conductor
🤡The maximum assigned temperature of the cable conductor is : XLPE insulated is 90℃, PVC insulated is70℃.
🍷漏电时(较长保持时期不少于5s)电力电缆导体的最好热度不低于: 化学交联聚丁二烯隔绝250℃, 聚氯丁二烯隔绝160℃。
🅷During having a short circuit, lasting less than 5 seconds, the maximum temperature of the cable conductor shall not be above: XLPE insulated is 250℃, PVC insulated is160℃
3、 敷设区域环境温湿度Ambient temperature for laying
数据线敷设时的室内环境温湿度应不超过0℃,反之要求前提升温。
🎀During the cable laying, the ambient temperature must be above 0℃,if not the cable need be preheated.
4、 按照内弯弧长The bend radius
安装程序时高压电缆不大变形直径见表2.
The minimum bending diameter must be above the following standard:表2 电缆线使用时最窄曲折弧长
Table2 The minimun bend radius of the cable建设项目Item | 单芯电览single core cable | 三芯电缆线 triple core cable | ||
无铠装 no amour | 有铠装 with amour | 无铠装 no amour | 有铠装 with amour | |
安转时的通信电缆世界上最大变形表面积 Minimun bend radius of the cable in course of installation | 20D | 15D | 15D | 12D |
较近连结盒和终高端的高压电缆的最短弯度圆弧 The minimun bend radius of the cable close to the junction box and terminal | 15D | 12D | 12D | 10D |
🐓注:D为高压电缆外径(mm)。Note:D is outer diameter of the cable |
5、 敷设方式
🔥电缆电线不会有敷设高差被限。There is no limit of head drop during the cable laying.
电力电缆同意敷修在室内装修、室处、空气的结合土地中,同意轮廓线有污水。
The cable may be laid in indoor, outdoor, air and soil. The cable may be immersed in water locally.✤低压电览线敷设的方法可是所谓的隧道、地埋管、低压电览线沟、电线桥架、管沟,铠装低压电览线不得直埋下水道,材料铠装低压电览线不得平行敷设。
The cable may be laid in tunnel, pipe, trench, conduit and on cable bridge. The amoured cable can be laid undergroud, and the wire- amoured cable can be laid vertically.单芯电线电缆不不可以敷选在磁铁合金管外。
The single core cable mustn't be laid in the magnetic metal pipes.电览敷设周围环境应具比较好的散热性能标准。
The enviroment of cable laying shall be in good heat dissipation condition.6、 线缆敷设时导体非常大能接受腰椎牵地心引力和线缆非常大能接受侧负担
The maxium allowed haul-off force and lateral pressure of cable𓄧导体最大的不可以迁地心引力计算的方法:he calculating method of the maxium allowed haul-off force :
——铜导体:F=70×S(N/mm2)。
——铝导体:F=40×S(N/mm2)。
꧟侧工作压力计算方式方式:the calculating method of the maxium allowed lateral pressure:
💯P=F÷R(N/m),较大合法侧压强不不低于3000N/m。the maxium allowed lateral pressure≤3000N/m
式中:F-牵引机力,N;lateral pressure
S-导体截面积,mm2;conductor section
P-侧气压,N/m;lateral pressure
R-电缆电线曲折圆的直径,m。Bend radius
🅠7、 缆线车辆和保存需要the requirements on transportation and storage:
🌳线缆盘不能接受平放。The cable reels shall not be delivered and stored in flat state
🌸装运中禁令从最高处丢下装配有电线的电线盘,禁令物理挫伤电线。It is strictly forbidden to push the cable reel from the high level in order to prevent the cable from damages
高压缆线假若需按段的使用,高压缆线按段后一定要用防水胶封帽将高压缆线头密封,控制漏水。
If the cable should be used sectionally, the head of the cable must be sealed in order to prevent water intake.1、简称Code
导体型号Conductor code
🧸铜导体(省略)Copper conductor ( omitted )………………………………………………………………T
♌铝导体aluminium conductor…………………………………………………………………………………L
电绝缘编号Insulation code
🍷化学交联聚氯乙烯隔热 cross-linking polyethylene(XLPE) insulated……………………………………………YJ
ꦚ聚氯丁二烯耐压 polyvinyl chloride (PVC) insulated……………………………………………V
绝缘护套简称1)Sheath code
🍌聚氯氯乙烯护线套 polyvinyl chloride and sheath………………………………………………………………V
🌞聚乙稀保护套 polyethylene sheath……………………………………………………………………………Y
铠装编号Amour code
ꦡ双尼龙带铠装steel tape armoured ……………………………………………………………………………2
外保护套编号Outer sheath code
💮聚氯丁二烯外护线套 polyvinyl chloride outer sheath …………………………………………………………2
﷽聚丁二烯外护线套 polyethylene outer sheath …………………………………………………………………3
ಞ铜带屏弊copper tape screen………………………………………………………………………………P2
注:Note
1) 🌠属于挤包的内衬层和隔开套等。Including the extruding inner covering and separating tape.
2、的产品表现策略Expressed method of product
💛品牌用技术参数型号查询(技术参数型号查询有自然数代號的电缆线外护层,自然数前的文本框代號表达出来内绝缘护套)、技术参数(额定功率工作电压、芯数、标称剖面)和基准产品编号表达出来。
The product is described as type (figure code of cable outer sheath, the word code in front of the figure means inner sheath), specification(rated voltage, cores numbers, sectioal area ) and standards code.3、产品的型号查询构成The consistant of specifications
產品机型的组合和编排依次下面:
The consistant of specification, as follow:
4、软件表现做法 Expressed method of product
举例:铜芯交连聚乙稀隔热聚氯乙稀保护套铜带屏弊供用电电缆线,额定值电流0.6/1kV,3+1芯,标称受力120mm2,碱式盐线受力70mm2,数字代表为:
YJVP2-0.6/1 3*120+1*70 Q/12BJ 5142-2003Example:Copper conductor XLPE insulated, copper tape screen and PVC sheathed power cables, rated Voltages 0.6/1kV, 3+1 cores, Nominal cross area 120mm2, see the following:
YJVP2-0.6/1 3*120+1*70 Q/12BJ 5142-20031、产品的类型Type of product
产品的较为常用形号见表3。
For the common product types , please see the table 3表3 的产品尺寸
Table 3 Type of product
应用 Type | 产 品 名 称 Name of product | 可用于条件及生态环境 Applicability and urroundings | |
铜 芯 Copper core | 铝 芯 Aluminium core | ||
YJVP2 | YJLVP2 | 化学交联聚丁二烯绝缘性聚氯丁二烯保护套铜带拦截电力设备数据线 🐼XLPE insulated PVC sheath copper tape screen power cable | 棚内、隧道口、通道、低压电缆管、桥架、排管等 🀅In a building, tunnel, pipe, trench and so on |
YJVP2-22 | YJLVP2-22 | 化学交联聚乙稀绝缘电阻链条铠装聚氯乙稀保护套铜带屏蔽了低压电缆低压电缆 🍰XLPE insulated steel tape armoured PVC sheath copper tape screen power cable | |
VVP2 | VLVP2 | 聚氯乙稀隔热聚氯乙稀护线套铜带屏蔽掉电力能源电线电缆 🍸PVC insulated PVC sheath copper tape screen power cable | 🍌空间内、所谓的隧道、拖链管沟内,或埋地敷设等,能顶住必定物理外界,但可以顶住大的拉力。 For laying indoors 、 in tunnel, cable trench, or direct in ground,able to bear external mechanicalforces, but unable to bear large pulling force |
VVP2-22 | VLVP2-22 | 聚氯乙稀电绝缘带钢铠装聚氯乙稀护线套铜带闭屏电量的使用电线电缆 ☂PVC insulated steel tape armoured PVC sheath copper tape screen power cable |
2、货品产品规格 Specification of product
For product rated voltage, conductor sectiona and the numbers of cores, please see the table 4.表4 厂品产品规格
Table 4 Specification of prouduct型 号 Type | 芯数 Number of cores | 标称载面 Nominal cross area(㎜2) | |
YJVP2VVP2 | YJLVP2VLVP2 | 1 | 1.5-3002.5-300 |
YJVP2YJVP2-22VVP2VV2-22 | YJLVP2YJLVP2-22VLVP2VLV2-22 | 2345 | 1.5-3002.5-300 |
YJVP2YJVP2-22VVP2VV2-22 | YJLVP2YJLVP2-22VLVP2VLV2-22 | 4-300 | |
YJVP2YJVP2-22VVP2VV2-22 | YJLVP2YJLVP2-22VLVP2VLV2-22 | 3+14+13+2 | 4-300 |
1、导体conductor
ඣ导体应以符合标准GB/3956 的第一点种或第2种裸渗碳铜导体或烫金属层渗碳铜导体,或这两种方式最为的裸铝导体或断桥铝材料导体;一些第5种裸铜导体或电镀金属层退火处理铜导体。
The conductor shall meet the first one of the requirement of GB/3956 or the second one of that, that is bare anneal copper conductor, or bare aluminium conductor or aluminium alloy, or the fifth one of that, that is bare copper conductor or metal coated anneal copper conductor.2、电绝缘insutation
绝缘带性应密切挤包在导体上,且应轻松剥除而不损坏绝缘带性体、导体或铬层。
The insulation layer shall be extruded on the conductor, and it shall be easy to be stripped without damages on insulation, conductor and coating layer.3、屏避Screen
合金金属屏避高压电缆屏避层采用用软铜带,单双层重复绕包。ꦐThe screen layer shall be flexible copper tape with single overwrapping type.
4、防护套(有铠装电力电缆)Inner sheath(Armoured cables)
运用聚氯氯乙烯(PVC)或聚丁二烯(PE)挤包在缆芯上。
The separated sheath is the extruding PVE or PE on the cable cores5、 铠装Amour
多芯铠装低压电缆的铠装资料应当选用镀锌管钢表带。单芯铠装电线电缆的铠装应配用非吸引力装修材料。跟据手机用户请求必选用不透钢材质的带、铝带、锰钢属带或铜带,如无请求般应配用不透钢材质的带。The amour of the multiple cable shall be zinc-plated steel tape, but the amour of the single cable uesed in AC circuit shall be non-magnetic metal-tape or metal-wire. The tappering mode of metal tape should adopt double layer open tappering, and the mode of metal wire shall mutiple concentric stranding.💮注:海量其实介绍信,使用在一种独特构成铠装(如添加图片金属丝的隔磁构成)的单芯电览使用在交流活动回路开关时均出現电览变烫引起载流量数据大有骤降的的现象,因为不网友推荐使用在。
Note: A large number of facts show that the single cable with the special structure amour in the AC circuit exists the heating phenomenon, thus causing the reduction of current capacity. The manufacturer don't suggest to adopt this kind cable.
6、 外护线套outer sheath
用到ST2型聚氯丁二烯护线套料或ST7型聚氯乙烯(PE)绝缘护套料挤包在铠装、同德同心导体上。
The materials of outer sheath are extruding ST2 PVCor ST7 PV on amour, insulation or cable cores.
7、生产设备电力电缆的标志图片Cable marks
生产设备数据线的外护线套外观印着厂名、类型、功率线电压、芯数、标称截面积和米数的反复logo。
The outer sheath of the cable shall have the following information printed at regular intervals throughtout the length of the cable:8、厂品结构的构造图Pictures of products structure
上图电览款式:YJVP2、YJLVP2、VVP2、VLVP2
Type of above the pictures:YJVP2、YJLVP2、VVP2、VLVP2
💖1—导体 Conductore 4—铜带闭屏
🎶2—绝缘性 Insulation 5—绝缘护套 Sheath
ꦦ3—包带
上图电览具体型号:YJVP2-22、YJLVP2-22、VVP2-22、VLVP2-22
Type of above the pictures:YJVP2-22、YJLVP2-22、VVP2-22、VLVP2-22
♓1—导体 Conductore 5—内衬层 Inner covering
꧃2—绝缘性 Insulation 6—铠装Armor
🥃3—包带 7—绝缘护套 Sheath
🌳4—铜带屏弊
缆线一般高技术特点主要参数见表5~6。
For the parameters of technical performance index of cables, please see talbe 5-6表5 电力电缆万能技木性能方面性能指标
Table 5 The parameters of technical performance index of cables编号Order | 产品Item | 企事业单位Unit | 招生指标Indicator |
1 | 导体电流电阻值 D.C. resistance of conductor | Ω/km | 见表6 see addenda A |
2 | 绝缘带热敏电阻常数(20℃,是较为小的) Constant of insulation resistance (20°C, minimum) | MΩ/km | 3.67 |
3 | 交换相电压检验A.C. voltage test 现场实验相电压 test voltage 疲劳试验的时间 test duration 现场实验毕竟 test result | kVmin | 3.55 绝缘层不发生损坏 The insulation shall have no puncture |
4 | 四小时内高直流电压检测 Four-hours high voltage test试验报告电流 检验耗时 实验英文的结果 | kVh | 2.44 试件材料应不穿透 The sample shall have no puncture |
5 5.1 5.2 | 绝缘性热拓宽应力测试 insulation thermal elongation test耐压因素 test conditions 气流室温 air temperature 受力日期 loading time 自动化地应力 mechanical stress 根据下生长率(主要) Extensibility on load (max)冷却塔后永久性长度率(较大) Permanent extensibility after being cooled (max) | ℃ minN/cm2 % % | 200±3 1520175 15 |
表6 导体电阻功率
Table 6 Resistance of conductor导体标称断面/mm2 Nominal cross area of conductor/mm2 | 20℃导体电流阻值≤/Ω/km Resistanceof conductor in 20℃ ≤ | 导体座谈会电阻值/Ω/km Conductor AC resistance/Ω/km | ||
铜导体 Copper core | 铝导体 Aluminium core. | 铜导体 Copper core | 铝导体 Aluminium core. | |
1.5 | 12.1 | - | -- | -- |
2.5 | 7.41 | - | -- | -- |
4 | 4.61 | 7.41 | -- | -- |
6 | 3.08 | 4.61 | -- | -- |
10 | 1.83 | 3.08 | 2.333 | 3.964 |
16 | 1.15 | 1.91 | 1.466 | 2.458 |
25 | 0.727 | 1.20 | 0.927 | 1.54 |
35 | 0.524 | 0.868 | 0.668 | 1.11 |
50 | 0.387 | 0.641 | 0.493 | 0.822 |
70 | 0.268 | 0.443 | 0.342 | 0.568 |
95 | 0.193 | 0.320 | 0.347 | 0.411 |
120 | 0.153 | 0.253 | 0.196 | 0.325 |
150 | 0.124 | 0.206 | 0.159 | 0.265 |
185 | 0.0991 | 0.164 | 0.128 | 0.211 |
240 | 0.0754 | 0.125 | 0.0985 | 0.162 |
300 | 0.0601 | 0.100 | 0.0797 | 0.130 |
400 | 0.0470 | 0.0778 | 0.0640 | 0.102 |
500 | 0.0366 | 0.0605 | 0.0504 | 0.0799 |
630 | 0.0283 | 0.0469 | 0.0406 | 0.0634 |
800 | 0.0221 | 0.0367 | 0.0336 | 0.0509 |
表7 电力电缆电感
Table7 XLPE insulted copper tape screen Capacitance of cable导体标称横截面/ Nominal cross area of conductor/mm2 | 每相电阻/μF/km Capacitance of eath phase/μF/km | 导体标称载面/ Nominal cross area of conductor/mm2 | 每相电解电容/μF/km Capacitance of eath phase/μF/km | 导体标称受力/ Nominal cross area of conductor/mm2 | 每相电容(电容器)/μF/km Capacitance of eath phase/μF/km |
1.5 | 0.20 | 35 | 0.61 | 185 | 0.76 |
2.5 | 0.24 | 50 | 0.63 | 240 | 0.82 |
4 | 0.29 | 70 | 0.69 | 300 | 0.86 |
6 | 0.34 | 95 | 0.80 | 400 | 0.88 |
10 | 0.47 | 120 | 0.82 | 500 | 0.93 |
16 | 0.57 | 150 | 0.78 | 630 | 0.98 |
25 | 0.53 |
表8 聚氯乙稀绝缘带铜带手机屏蔽电缆线滤波电容
Table 8 PVC insulted copper tape screen Capacitance of cable导体标称载面/ Nominal cross area of conductor/mm2 | 每相电容器/μF/km Capacitance of eath phase/μF/km | 导体标称断面/ Nominal cross area of conductor/mm2 | 每相电感/μF/km Capacitance of eath phase/μF/km | 导体标称截面积/ Nominal cross area of conductor/mm2 | 每相滤波电容/μF/km Capacitance of eath phase/μF/km |
1.5 | 0.58 | 35 | 1.51 | 240 | 2.08 |
2.5 | 0.69 | 50 | 1.5 | 300 | 2.12 |
4 | 0.70 | 70 | 1.75 | 400 | 2.21 |
6 | 0.82 | 95 | 1.81 | 500 | 2.34 |
10 | 1.11 | 120 | 2.01 | 630 | 2.63 |
16 | 1.35 | 150 | 1.98 | 800 | 2.92 |
25 | 1.32 | 185 | 1.99 |
表9 热塑聚氯乙烯绝缘层电抗
Table 9 XLPE insulted eactanceo f cable (Ω/km)
导体标称剖面/ Nominal cross area of conductor/mm2 | 电抗/Ω/km Reactance (Ω/km) | ||||
YJVP2、YJLVP2 (单芯Sing core) | YJVP2、YJLVP2 YJVP2-22、YJLVP2-22、 (两芯Two cores) | YJVP2、YJLVP2 YJVP2-22、YJLVP2-22、 (三芯、四芯3cores、4芯) | YJVP2、YJLVP2 YJVP2-22、YJLVP2-22 (3+1芯、3+1 cores) | YJVP2、YJLVP2 YJVP2-22、YJLVP2-22 (3+2芯、4+1芯、5芯、3+2 cores、4+1cores、5 cores) | |
1.5 | 0.122 | 0.103 | 0.103 | - | - |
2.5 | 0.115 | 0.0957 | 0.0957 | - | - |
4 | 0.109 | 0.0897 | 0.0897 | 0.0897 | 0.0897 |
6 | 0.104 | 0.0850 | 0.0850 | 0.0850 | 0.0850 |
10 | 0.101 | 0.0823 | 0.0823 | 0.0823 | 0.0823 |
16 | 0.0978 | 0.0789 | 0.0789 | 0.0789 | 0.0789 |
25 | 0.0990 | 0.0801 | 0.0801 | 0.0801 | 0.0801 |
35 | 0.0969 | 0.0780 | 0.0780 | 0.0780 | 0.0780 |
50 | 0.0937 | 0.0313 | 0.0313 | 0.0313 | 0.0748 |
70 | 0.0925 | 0.0300 | 0.0300 | 0.0300 | 0.0736 |
95 | 0.0908 | 0.0284 | 0.0284 | 0.0284 | 0.0720 |
120 | 0.0898 | 0.0274 | 0.0274 | 0.0274 | 0.0709 |
150 | 0.0903 | 0.0279 | 0.0279 | 0.0279 | 0.0714 |
185 | 0.0905 | 0.0281 | 0.0281 | 0.0281 | 0.0717 |
240 | 0.0893 | - | 0.0269 | 0.0269 | 0.0704 |
300 | 0.0874 | - | 0.0263 | 0.0263 | 0.0699 |
400 | 0.0857 | - | - | - | - |
500 | 0.0882 | - | - | - | - |
630 | 0.0873 | - | - | - |
表10 聚氯丁二烯耐压电抗
Table 10 PVC insulted eactanceo f cable (Ω/km)
导体标称截面积/ Nominal cross area of conductor/mm2 | 电抗/Ω/km Reactance (Ω/km) | ||||
VVP2、VLVP2 (单芯Sing core) | VVP2、VLVP2 VVP2-22VLVP2-22(两芯Two cores) | VVP2、VLVP2 VVP2-22VLVP2-22(三芯、四芯3cores、4芯) | VVP2、VLVP2 VVP2-22VLVP2-22(3+1芯、3+1 cores) | VVP2、VLVP2 VVP2-22VLVP2-22(3+2芯、4+1芯、5芯、3+2 cores、4+1cores、5 cores) | |
1.5 | 0.152 | 0.0108 | 0.108 | - | - |
2.5 | 0.136 | 0.0996 | 0.0996 | - | - |
4 | 0.131 | 0.0992 | 0.0992 | 0.0992 | 0.0992 |
6 | 0.126 | 0.0935 | 0.0935 | 0.0935 | 0.0935 |
10 | 0.114 | 0.0889 | 0.0889 | 0.0889 | 0.0889 |
16 | 0.106 | 0.0844 | 0.0844 | 0.0844 | 0.0844 |
25 | 0.107 | 0.0848 | 0.0848 | 0.0848 | 0.0848 |
35 | 0.103 | 0.0822 | 0.0822 | 0.0822 | 0.0822 |
50 | 0.0954 | 0.0796 | 0.0796 | 0.0796 | 0.0796 |
70 | 0.0912 | 0.0766 | 0.0766 | 0.0966 | 0.0966 |
95 | 0.0891 | 0.0764 | 0.0764 | 0.0764 | 0.0764 |
120 | 0.0854 | 0.0741 | 0.0741 | 0.0741 | 0.0741 |
150 | 0.0873 | 0.0743 | 0.0743 | 0.0743 | 0.0743 |
185 | 0.0857 | 0.0742 | 0.0742 | 0.0742 | 0.0742 |
240 | 0.0839 | - | 0.0732 | 0.0732 | 0.0732 |
300 | 0.0834 | - | 0.0729 | 0.0729 | 0.0729 |
400 | 0.0816 | - | - | ||
500 | 0.0803 | - | - | ||
630 | 0.0781 | - | - | ||
800 | 0.0755 | - | - |
表11 无铠装电线载国内流量
Table 11 Current carrying of Unarmored cable适用人群电线机型:YJVP2、YJLVP2
Applicable cable types: YJVP2、YJLVP2
导体是最高的合法事情气温:90℃
💖The maximum assigned temperature of the conductor is90℃.
工作环境热度:25℃
Ambient temperature:25℃
土壤环境散热量因子:120℃·cm/W
Soil thermal resistivity 120℃·cm/W
导体 横截面 mm2 Conductor cross area mm2 | 气体中敷设长远陆续承载合法载用户量(A) 🔯Laying long-term continuous load allowable current-carrying capacity in the air (A) | 直埋敷设长期的间隔热负荷不得载水流量(A) ౠDirect-buried laying long-term continuous load allowable current-carrying capacity (A) | ||||||||||||||
铜芯Copper core | 铝芯Aluminium core. | 铜芯Copper core | 铝芯Aluminium core. | |||||||||||||
单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | |
1.5 | 27.6 | 22.8 | 19.2 | 23 | -- | -- | -- | -- | 37.2 | 28.8 | 24 | -- | -- | -- | -- | -- |
2.5 | 38.4 | 31.2 | 26.4 | 35 | 28.8 | 24 | 19.2 | 26 | 50.4 | 38.4 | 32.4 | 33 | 38.4 | 28.8 | 24 | 25 |
4 | 49.2 | 42 | 34.8 | 34.8 | 37.2 | 31.2 | 26.4 | 26.4 | 67.2 | 49.2 | 42 | 42 | 51.6 | 38.4 | 32.4 | 32.4 |
6 | 64.8 | 52.8 | 45.6 | 45.6 | 49.2 | 40.8 | 34.8 | 34.8 | 84 | 62.4 | 52.8 | 52.8 | 64.8 | 48 | 40.8 | 40.8 |
10 | 86.4 | 72 | 62.4 | 61.2 | 66 | 55.2 | 48 | 48 | 112.8 | 82.8 | 70.8 | 69.2 | 86.4 | 63.6 | 55.2 | 54 |
16 | 116.4 | 94.8 | 82.8 | 81.6 | 88.8 | 73.2 | 63.6 | 63.6 | 148.8 | 109.2 | 92.4 | 91.2 | 114 | 84 | 70.8 | 69.6 |
25 | 146.4 | 128.4 | 111.6 | 110.4 | 122.4 | 99.6 | 86.4 | 85.2 | 195.6 | 141.6 | 121.2 | 120 | 150 | 109.2 | 93.6 | 92.4 |
35 | 194.4 | 148.8 | 135.6 | 138 | 148.8 | 114 | 104.4 | 106.8 | 235.2 | 166.8 | 148.8 | 147.6 | 181.2 | 128.4 | 114 | 114 |
50 | 244.8 | 186 | 168 | 172.8 | 188.4 | 144 | 129.6 | 133.2 | 289.2 | 205.2 | 180 | 182.4 | 222 | 158.4 | 139.2 | 140.4 |
70 | 303.6 | 235.2 | 210 | 213.6 | 234 | 181.2 | 162 | 163.2 | 350.4 | 249.6 | 220.8 | 219.6 | 270 | 192 | 169.2 | 168 |
95 | 326.4 | 285.6 | 256.8 | 261.6 | 256.8 | 218.4 | 198 | 201.6 | 417.6 | 308.4 | 261.6 | 261.6 | 320.4 | 229.2 | 201.6 | 200.4 |
120 | 427.2 | 327.6 | 296.4 | 302.4 | 331.2 | 253.2 | 229.2 | 234 | 470.4 | 338.4 | 296.4 | 297.6 | 366 | 261.6 | 228 | 230.4 |
150 | 492 | 378 | 351.6 | 356.4 | 379.2 | 290.4 | 270 | 273.6 | 536.4 | 386.4 | 339.6 | 343.2 | 411.6 | 297.6 | 261.6 | 264 |
185 | 558 | 400 | 398.4 | 409.2 | 429.6 | 322 | 308.4 | 315.6 | 600 | 386 | 381.6 | 385.2 | 462 | 340 | 296.4 | 297.6 |
240 | 662.4 | 479 | 396 | 396 | 510 | 383 | 367.2 | 355.2 | 698.4 | 446 | 441.6 | 398 | 536.4 | 400 | 340.8 | 327.6 |
300 | 763.2 | 522 | 452 | 457 | 588 | 487 | 361 | 348 | 792 | 507 | 430 | 430 | 600 | 510 | 430 | 450 |
400 | 908.4 | -- | -- | -- | 706.8 | -- | -- | -- | 927.6 | -- | -- | -- | 711.6 | -- | -- | -- |
500 | 1063.2 | -- | -- | -- | 816 | -- | -- | -- | 1051.2 | -- | -- | -- | 804 | -- | -- | -- |
630 | 1230 | -- | -- | -- | 944.4 | -- | -- | -- | 1200 | -- | -- | -- | 920.4 | -- | -- | -- |
800 | 1605.6 | -- | -- | -- | 1120.8 | -- | -- | -- | 1383.6 | -- | -- | -- | 1062 | -- | -- | -- |
表12 铠装电缆线载流量的
Table 12 Current carrying of armored cable采用电缆电线主要参数:YJVP2-22、YJLVP2-22
Applicable cable types: YJVP2-22、YJLVP2-22
导体更高充许工作的温湿度:90℃
🌄The maximum assigned temperature of the conductor is90℃.
区域气温:25℃
Ambient temperature:25℃
土地传热弹性系数弹性系数:120℃·cm/W
Soil thermal resistivity 120℃·cm/W
导体 受力 mm2 Conductor cross area mm2 | 空气质量中敷设经常多次负担允许的载人流量(A) Laying long-term continuous load allowable current-carrying capacity in the air (A) | 直埋敷设暂时间断性承载不可以载客流量(A) 🃏Direct-buried laying long-term continuous load allowable current-carrying capacity (A) | ||||||||||
铜芯Copper core | 铝芯Aluminium core. | 铜芯Copper core | 铝芯Aluminium core. | |||||||||
二芯 2-cores | 三芯 3-cores | 四芯4-cores | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | |
4 | 43.2 | 37.2 | 36 | 32.4 | 27.6 | 27.6 | 49.2 | 42 | 40.8 | 38.4 | 32.4 | 31.2 |
6 | 54 | 46.8 | 46.8 | 42 | 36 | 36 | 62.4 | 54 | 52.8 | 48 | 40.8 | 40.8 |
10 | 72 | 62.4 | 62.4 | 55.2 | 48 | 48 | 80.4 | 70.8 | 69.2 | 62.4 | 55.2 | 54 |
16 | 97.2 | 85.2 | 84 | 74.4 | 64.8 | 64.8 | 108 | 93.6 | 92.4 | 84 | 72 | 70.8 |
25 | 127.2 | 115.2 | 112.8 | 97.2 | 87.6 | 87.6 | 141.6 | 123.6 | 120 | 109.2 | 94.8 | 92.4 |
35 | 153.6 | 136.8 | 142.8 | 118.8 | 105.6 | 110.4 | 168 | 147.6 | 151.2 | 129.6 | 112.8 | 116.4 |
50 | 192 | 172.8 | 178.8 | 147.6 | 133.2 | 138 | 205.2 | 181.2 | 184.8 | 158.4 | 139.2 | 141.6 |
70 | 236.4 | 214.8 | 220.8 | 182.4 | 165.6 | 169.2 | 248.4 | 230.4 | 222 | 192 | 170.4 | 170.4 |
95 | 288 | 260.4 | 271.2 | 222 | 200.4 | 208.8 | 297.6 | 259.2 | 265.2 | 229.2 | 199.2 | 205.2 |
120 | 333.6 | 302.4 | 312 | 258 | 232.8 | 241.2 | 340.8 | 296.4 | 302.4 | 262.8 | 228 | 232.8 |
150 | 382.8 | 350.4 | 361.2 | 295.2 | 270 | 277.2 | 384 | 338.4 | 340.8 | 295.2 | 259.2 | 261.6 |
185 | 400 | 339 | 339 | 322 | 262 | 265 | 420 | 420 | 420 | 300 | 275 | 275 |
240 | 479 | 396 | 396 | 383 | 309 | 309 | 500 | 500 | 500 | 340 | 320 | 320 |
表13 无铠装通信电缆载精准流量
Table 13 Current carrying of Unarmored cable适宜拖链电缆技术参数: VVP2、VLVP2
Applicable cable types: VVP2、VLVP2
导体更高支持工作上溫度:70℃
🎃The maximum assigned temperature of the conductor is70℃.
生态环境热度:25℃
Ambient temperature:25℃
土壤层热导率标准值:120℃·cm/W
Soil thermal resistivity 120℃·cm/W
体 断面 mm2 Conductor cross area mm2 | 空气的中敷设长远不间断用电负荷准许载2g流量(A) Laying long-term continuous load allowable current-carrying capacity in the air (A) | 直埋敷设长年不间断短路电流同意载的流量(A) ▨Direct-buried laying long-term continuous load allowable current-carrying capacity (A) | ||||||||||||||
铜芯Copper core | 铝芯Aluminium core. | 铜芯Copper core | 铝芯Aluminium core. | |||||||||||||
单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 单芯 Single-core | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | |
1.5 | 23 | 19 | 16 | 15 | — | 31 | 24 | 20 | 22 | |||||||
2.5 | 32 | 26 | 22 | 19 | 24 | 20 | 16 | 15 | 42 | 32 | 27 | 29 | 32 | 24 | 20 | 25 |
4 | 41 | 35 | 29 | 29 | 31 | 26 | 22 | 22 | 56 | 41 | 35 | 35 | 43 | 32 | 27 | 27 |
6 | 54 | 44 | 38 | 38 | 41 | 34 | 29 | 29 | 70 | 52 | 44 | 44 | 54 | 40 | 34 | 34 |
10 | 72 | 60 | 52 | 51 | 55 | 46 | 40 | 40 | 94 | 69 | 59 | 58 | 72 | 53 | 46 | 45 |
16 | 97 | 79 | 69 | 68 | 74 | 61 | 53 | 53 | 124 | 91 | 77 | 76 | 95 | 70 | 59 | 58 |
25 | 122 | 107 | 93 | 92 | 102 | 83 | 72 | 71 | 163 | 118 | 101 | 100 | 125 | 91 | 78 | 77 |
35 | 162 | 124 | 113 | 115 | 124 | 95 | 87 | 89 | 196 | 139 | 124 | 123 | 151 | 107 | 95 | 95 |
50 | 204 | 155 | 140 | 144 | 157 | 120 | 108 | 111 | 241 | 171 | 150 | 152 | 185 | 132 | 116 | 117 |
70 | 253 | 196 | 175 | 178 | 195 | 151 | 135 | 136 | 292 | 208 | 184 | 183 | 225 | 160 | 141 | 140 |
95 | 272 | 238 | 214 | 218 | 214 | 182 | 165 | 168 | 348 | 257 | 218 | 218 | 267 | 191 | 168 | 167 |
120 | 356 | 273 | 247 | 252 | 276 | 211 | 191 | 195 | 392 | 282 | 247 | 248 | 305 | 218 | 190 | 192 |
150 | 410 | 315 | 293 | 297 | 316 | 242 | 225 | 228 | 447 | 322 | 283 | 286 | 343 | 248 | 218 | 220 |
185 | 465 | 320 | 332 | 341 | 358 | 251 | 257 | 263 | 500 | 395 | 318 | 321 | 385 | 310 | 247 | 248 |
240 | 552 | -- | 396 | -- | 425 | -- | 306 | -- | 582 | -- | 368 | -- | 447 | -- | 284 | -- |
300 | 636 | -- | -- | -- | 490 | -- | -- | -- | 660 | -- | -- | -- | 500 | -- | -- | -- |
400 | 757 | -- | -- | -- | 589 | -- | -- | -- | 773 | -- | -- | -- | 593 | -- | -- | -- |
500 | 886 | -- | -- | -- | 680 | -- | -- | -- | 876 | -- | -- | -- | 670 | -- | -- | -- |
630 | 1025 | -- | -- | -- | 787 | -- | -- | -- | 1000 | -- | -- | -- | 767 | -- | -- | -- |
800 | 1338 | -- | -- | -- | 934 | -- | -- | -- | 1153 | -- | -- | -- | 885 | -- | -- | -- |
表14 铠装电览载视频流量
Table 14 Current carrying of armored cable选用线缆产品型号:VVP2-22、VLVP2-22
Applicable cable types: VVP2-22、VLVP2-22
导体最多准许业务气温:70℃
🃏The maximum assigned temperature of the conductor is70℃.
坏境工作温度:25℃
Ambient temperature:25℃
森林土壤散热量因子:120℃·cm/W
Soil thermal resistivity 120℃·cm/W
体 横截面 mm2 Conductor cross area mm2 | 室内空气中敷设长期性的多次工况支持载联通流量(A) Laying long-term continuous load allowable current-carrying capacity in the air (A) | 直埋敷设常期间断性变压器容量能载国内流量(A) ♊Direct-buried laying long-term continuous load allowable current-carrying capacity (A) | ||||||||||
铜芯Copper core | 铝芯Aluminium core. | 铜芯Copper core | 铝芯Aluminium core. | |||||||||
二芯 2-cores | 三芯 3-cores | 四芯4-cores | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | 二芯 2-cores | 三芯 3-cores | 四芯4-cores | |
4 | 36 | 31 | 30 | 27 | 23 | 23 | 41 | 35 | 34 | 32 | 27 | 26 |
6 | 45 | 39 | 39 | 35 | 30 | 30 | 52 | 45 | 44 | 40 | 34 | 34 |
10 | 60 | 52 | 52 | 46 | 40 | 40 | 67 | 59 | 58 | 52 | 46 | 45 |
16 | 81 | 71 | 70 | 62 | 54 | 54 | 90 | 78 | 77 | 70 | 60 | 59 |
25 | 106 | 96 | 94 | 81 | 73 | 73 | 118 | 103 | 100 | 91 | 79 | 77 |
35 | 128 | 114 | 119 | 99 | 88 | 92 | 140 | 123 | 126 | 108 | 94 | 97 |
50 | 160 | 144 | 149 | 123 | 111 | 115 | 171 | 151 | 154 | 132 | 116 | 118 |
70 | 197 | 179 | 184 | 152 | 138 | 141 | 207 | 192 | 185 | 160 | 142 | 142 |
95 | 240 | 217 | 226 | 185 | 167 | 174 | 248 | 216 | 221 | 191 | 166 | 171 |
120 | 278 | 252 | 260 | 215 | 194 | 201 | 284 | 247 | 252 | 219 | 190 | 194 |
150 | 319 | 292 | 301 | 246 | 225 | 231 | 320 | 282 | 284 | 246 | 216 | 218 |
185 | 326 | 333 | 345 | 251 | 257 | 266 | 395 | 315 | 319 | 310 | 242 | 246 |
240 | -- | 392 | -- | -- | 305 | -- | -- | 364 | -- | -- | 295 | -- |
多种土壤中湿度下载地址流量数据的改正标准值
Current rating for variation in soil temperature
泥土室内温度 Soil temperature | 20 ℃ | 25 ℃ | 30 ℃ | 35 ℃ | 40 ℃ |
计算指数 Rating factor | 1.04 | 1.0 | 0.96 | 0.92 | 0.87 |
电线电缆的构成规格尺寸见表15~表30。
Configuration measurements of the cable,see the table15~ table30表15 0.6/1kV化学交联聚氯乙烯绝缘带铜带屏弊用电电缆电线
Table15 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称横截面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
测算外径 Calculated external diameter (mm) | 计算出含水量 Calculated weight (kg/km) | 计算方式外径 Calculated external diameter (mm) | 计算载重量 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
1*6 | 7.1 | 106 | 68 | - | - | - |
1*10 | 8.3 | 153 | 91 | 12.2 | 276 | 215 |
1*16 | 9.5 | 213 | 118 | 13.3 | 350 | 255 |
1*25 | 11.1 | 315 | 164 | 15.0 | 473 | 322 |
1*35 | 11.8 | 406 | 196 | 15.6 | 572 | 362 |
1*50 | 13.3 | 533 | 248 | 17.1 | 717 | 432 |
1*70 | 15.1 | 739 | 327 | 18.9 | 946 | 533 |
1*95 | 16.8 | 991 | 419 | 20.5 | 1213 | 641 |
1*120 | 18.5 | 1235 | 512 | 22.1 | 1471 | 749 |
1*150 | 20.6 | 1514 | 625 | 24.1 | 1769 | 879 |
1*185 | 22.7 | 1877 | 765 | 26.0 | 2143 | 1031 |
1*240 | 25.3 | 2430 | 967 | 28.6 | 2723 | 1261 |
1*300 | 27.9 | 3016 | 1181 | 31.1 | 3338 | 1503 |
1*400 | 31.6 | 3986 | 1566 | 34.7 | 4345 | 1925 |
表16 0.6/1kV热塑聚氯乙烯隔绝铜带屏弊电力设备电线电缆
Table16 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称剖面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算外径 Calculated external diameter (mm) | 计算出总重 Calculated weight (kg/km) | 算出外径 Calculated external diameter (mm) | 测算克重 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
2*2.5 | 10.5 | 151 | 120 | 13.7 | 275 | 244 |
2*4 | 11.4 | 194 | 144 | 14.6 | 328 | 278 |
2*6 | 12.5 | 248 | 173 | 15.7 | 393 | 318 |
2*10 | 14.9 | 361 | 238 | 18.1 | 532 | 409 |
2*16 | 17.2 | 503 | 312 | 20.4 | 697 | 507 |
2*25 | 20.5 | 718 | 414 | 23.7 | 947 | 643 |
2*35 | 21.8 | 934 | 512 | 25.0 | 1177 | 755 |
2*50 | 19.2 | 1082 | 509 | 22.4 | 1298 | 726 |
2*70 | 21.8 | 1499 | 671 | 25.2 | 1752 | 924 |
2*95 | 24.7 | 2014 | 866 | 28.0 | 2298 | 1149 |
2*120 | 27.3 | 2511 | 1060 | 31.9 | 2821 | 1371 |
2*150 | 30.7 | 3129 | 1343 | 35.5 | 3485 | 1699 |
2*185 | 33.9 | 3877 | 1644 | 38.9 | 4652 | 2419 |
表17 0.6/1kV化学交联聚乙稀隔绝铜带拦截电网通信电缆
Table17 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称剖面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
核算外径 Calculated external diameter (mm) | 算重量体积 Calculated weight (kg/km) | 计算出来外径 Calculated external diameter (mm) | 计算方法容量 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
3*2.5 | 10.9 | 187 | 140 | 14.3 | 318 | 271 |
3*4 | 11.8 | 241 | 166 | 15.2 | 381 | 305 |
3*6 | 13.1 | 317 | 205 | 16.3 | 469 | 356 |
3*10 | 15.8 | 484 | 300 | 19.0 | 664 | 480 |
3*16 | 18.2 | 660 | 375 | 21.4 | 865 | 579 |
3*25 | 21.7 | 991 | 534 | 24.9 | 1233 | 777 |
3*35 | 23.1 | 1269 | 636 | 26.2 | 1521 | 888 |
3*50 | 24.0 | 1589 | 730 | 27.4 | 1866 | 1008 |
3*70 | 27.1 | 2212 | 970 | 30.5 | 2523 | 1281 |
3*95 | 31.1 | 3027 | 1304 | 35.7 | 3720 | 1997 |
3*120 | 34.4 | 3769 | 1593 | 39.1 | 4540 | 2365 |
3*150 | 36.9 | 4603 | 1924 | 41.8 | 5440 | 2761 |
3*185 | 41.0 | 5712 | 2362 | 46.1 | 6652 | 3303 |
3*240 | 45.8 | 7397 | 2992 | 51.1 | 8459 | 4054 |
3*300 | 50.6 | 9176 | 3649 | 56.1 | 10363 | 4836 |
表18 0.6/1kV热塑聚氯乙烯绝缘性铜带屏蔽掉电力能源电揽
Table18 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称断面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算出外径 Calculated external diameter (mm) | 测算承重 Calculated weight (kg/km) | 测算外径 Calculated external diameter (mm) | 核算含量 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
4*2.5 | 11.7 | 228 | 166 | 15.0 | 366 | 303 |
4*4 | 12.8 | 298 | 198 | 16.1 | 448 | 348 |
4*6 | 14.0 | 399 | 249 | 17.4 | 562 | 412 |
4*10 | 17.0 | 592 | 346 | 20.4 | 786 | 540 |
4*16 | 19.7 | 847 | 466 | 23.0 | 1021 | 640 |
4*25 | 23.7 | 1249 | 671 | 27.0 | 1465 | 857 |
4*35 | 25.2 | 1568 | 803 | 28.7 | 1854 | 1009 |
4*50 | 25.9 | 2071 | 926 | 29.4 | 2371 | 1226 |
4*70 | 29.9 | 2946 | 1290 | 34.8 | 3618 | 1963 |
4*95 | 33.3 | 3955 | 1659 | 38.3 | 4710 | 2413 |
4*120 | 36.4 | 4928 | 2027 | 41.6 | 5761 | 2860 |
5*150 | 40.7 | 6056 | 2484 | 46.1 | 6994 | 3422 |
4*185 | 46.3 | 7541 | 3075 | 51.9 | 8619 | 4153 |
4*240 | 50.9 | 9758 | 3884 | 56.7 | 10962 | 5088 |
4*300 | 55.6 | 12085 | 4716 | 61.7 | 13418 | 6049 |
表19 0.6/1kV化学交联聚乙稀绝缘电阻铜带手机屏蔽供电局电览
Table19 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称断面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算方式外径 Calculated external diameter (mm) | 运算克重 Calculated weight (kg/km) | 估算外径 Calculated external diameter (mm) | 来计算体积 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
5*1.5 | 11.7 | 207 | 160 | 14.9 | 310 | 296 |
5*2.5 | 12.7 | 268 | 190 | 15.9 | 379 | 338 |
5*4 | 14.0 | 355 | 229 | 17.2 | 474 | 390 |
5*6 | 15.4 | 478 | 290 | 18.6 | 607 | 466 |
5*10 | 18.7 | 707 | 400 | 21.9 | 859 | 611 |
5*16 | 21.7 | 995 | 519 | 24.9 | 1168 | 762 |
5*25 | 26.2 | 1503 | 742 | 29.4 | 1709 | 1034 |
5*35 | 28.0 | 1965 | 910 | 31.3 | 2194 | 1231 |
表20 0.6/1kV化学交联聚丁二烯绝缘带铜带屏避功率电缆线
Table29 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称截面积 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
算外径 Calculated external diameter (mm) | 算起权重 Calculated weight (kg/km) | 估算外径 Calculated external diameter (mm) | 估算总重量 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
3*4+1*2.5 | 12.6 | 281 | 190 | 15.8 | 427 | 336 |
3*6+1*4 | 13.9 | 376 | 239 | 17.1 | 536 | 398 |
3*10+1*6 | 16.4 | 546 | 324 | 19.6 | 732 | 511 |
3+16+1*10 | 19.1 | 750 | 441 | 22.3 | 965 | 657 |
3*25+1*16 | 22.8 | 1109 | 627 | 26.0 | 1363 | 881 |
3*35+1*16 | 24.0 | 1385 | 726 | 27.1 | 1648 | 989 |
3*50+1*25 | 23.7 | 1829 | 834 | 27.0 | 2103 | 1107 |
3*70+1*35 | 26.6 | 2539 | 1101 | 30.0 | 2844 | 1407 |
3*95+1*50 | 31.4 | 3468 | 1475 | 36.0 | 4147 | 2153 |
3*120+1*70 | 34.1 | 4410 | 1837 | 38.9 | 5181 | 2607 |
3*150+1*70 | 38.3 | 5266 | 2189 | 43.3 | 6139 | 3061 |
3*185+1*195 | 42.4 | 6616 | 2709 | 47.6 | 7590 | 3682 |
3*240+1*120 | 47.2 | 8530 | 3417 | 52.5 | 9628 | 4514 |
3*300+1*150 | 52.7 | 10578 | 4175 | 58.3 | 11821 | 5419 |
表21 0.6/1kV热塑聚乙稀电绝缘铜带屏蔽了能量电线
Table21 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称受力 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
折算外径 Calculated external diameter (mm) | 来计算总重 Calculated weight (kg/km) | 折算外径 Calculated external diameter (mm) | 计算方法称重 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
4*4+1*2.5 | 13.7 | 337 | 212 | 16.9 | 495 | 370 |
4*6+1*4 | 15.1 | 456 | 270 | 18.3 | 628 | 442 |
4*10+1*6 | 18.0 | 663 | 366 | 21.2 | 866 | 570 |
4+16+1*10 | 21.1 | 937 | 479 | 24.3 | 1173 | 715 |
4*25+1*16 | 25.3 | 1404 | 680 | 28.5 | 1682 | 958 |
4*35+1*16 | 26.6 | 1767 | 807 | 30.0 | 2074 | 1113 |
4*50+1*25 | 29.4 | 2405 | 1085 | 32.8 | 2742 | 1421 |
4*70+1*35 | 33.8 | 3338 | 1445 | 38.5 | 4092 | 2198 |
4*95+1*50 | 38.1 | 4474 | 1860 | 42.9 | 5333 | 2719 |
4*120+1*70 | 42.4 | 5660 | 2312 | 47.4 | 6627 | 3279 |
4*150+1*70 | 46.9 | 6795 | 2771 | 52.1 | 7871 | 3847 |
4*185+1*195 | 51.8 | 8510 | 3428 | 57.1 | 9714 | 4632 |
4*240+1*120 | 59.1 | 11013 | 4367 | 64.7 | 12410 | 5763 |
4*300+1*150 | 64.7 | 13637 | 5323 | 70.6 | 15191 | 6877 |
表22 0.6/1kV交连聚氯乙烯隔热铜带禁掉通信电缆通信电缆
Table22 XLPE insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称截面积 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
核算外径 Calculated external diameter (mm) | 估算权重 Calculated weight (kg/km) | 来计算外径 Calculated external diameter (mm) | 计算公式称重 Calculated weight (kg/km) | |||
YJVP2 | YJLVP2 | YJVP2-22 | YJLVP2-22 | |||
3*4+2*2.5 | 13.5 | 320 | 214 | 16.7 | 475 | 369 |
3*6+2*4 | 14.8 | 434 | 271 | 18.0 | 603 | 441 |
3*10+2*6 | 17.4 | 619 | 360 | 20.6 | 815 | 556 |
3+16+2*10 | 20.5 | 880 | 472 | 23.7 | 1110 | 701 |
3*25+2*16 | 24.4 | 1305 | 658 | 27.5 | 1570 | 923 |
3*35+2*16 | 25.3 | 1572 | 798 | 28.7 | 1864 | 1089 |
3*50+2*25 | 27.2 | 2129 | 1017 | 30.6 | 2441 | 1329 |
3*70+2*35 | 31.1 | 2986 | 1322 | 35.7 | 3677 | 2013 |
3*95+2*50 | 35.7 | 3718 | 1723 | 40.5 | 4519 | 2524 |
3*120+2*70 | 40.0 | 5152 | 2149 | 44.9 | 6060 | 3057 |
3*150+2*70 | 42.6 | 5987 | 2480 | 47.7 | 6961 | 3454 |
3*185+2*195 | 47.6 | 7594 | 3096 | 52.8 | 8692 | 4194 |
3*240+2*120 | 54.8 | 9790 | 3935 | 60.2 | 11073 | 5218 |
3*300+2*150 | 59.6 | 12094 | 4781 | 63.1 | 13460 | 6148 |
表23 0.6/1kV聚氯氯乙烯绝缘性铜带拦截电览电览
Table23 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称断面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
算起外径 Calculated external diameter (mm) | 计算方式称重 Calculated weight (kg/km) | 运算外径 Calculated external diameter (mm) | 运算总重量 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
1*2.5 | - | - | - | - | - | - |
1*4 | - | - | - | - | - | - |
1*6 | 7.7 | 121 | 84 | - | - | |
1*10 | 8.9 | 171 | 110 | 12.9 | 278 | 216 |
1*16 | 10.1 | 234 | 139 | 14.1 | 354 | 259 |
1*25 | 11.7 | 343 | 192 | 15.7 | 484 | 332 |
1*35 | 12.4 | 439 | 229 | 16.4 | 588 | 378 |
1*50 | 14.0 | 585 | 300 | 18.1 | 756 | 471 |
1*70 | 15.7 | 791 | 379 | 19.7 | 979 | 567 |
1*95 | 17.8 | 1067 | 495 | 21.7 | 1273 | 702 |
1*120 | 19.3 | 1318 | 596 | 23.1 | 1537 | 815 |
1*150 | 21.5 | 1608 | 718 | 25.1 | 1844 | 955 |
1*185 | 23.6 | 1985 | 873 | 27.0 | 2236 | 1123 |
1*240 | 26.4 | 2574 | 1111 | 29.8 | 2853 | 1391 |
1*300 | 29.3 | 3192 | 1357 | 32.7 | 3501 | 1666 |
1*400 | 32.8 | 4197 | 1777 | 36.2 | 4539 | 2119 |
表24 0.6/1kV聚氯氯乙烯绝缘电阻铜带屏弊输配电电缆线
Table24 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称截面积 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算出外径 Calculated external diameter (mm) | 计算出总重 Calculated weight (kg/km) | 计算方法外径 Calculated external diameter (mm) | 算体重 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
2*1.5 | - | - | - | - | - | - |
2*2.5 | 10.9 | 165 | 134 | 14.1 | 293 | 262 |
2*4 | 12.6 | 226 | 176 | 15.8 | 373 | 322 |
2*6 | 13.7 | 283 | 208 | 16.9 | 440 | 365 |
2*10 | 16.1 | 402 | 279 | 19.3 | 585 | 462 |
2*16 | 18.4 | 549 | 359 | 21.6 | 756 | 566 |
2*25 | 21.7 | 778 | 473 | 24.9 | 1020 | 715 |
2*35 | 23.0 | 1000 | 578 | 26.2 | 1256 | 834 |
2*50 | 20.7 | 1178 | 606 | 24.1 | 1420 | 848 |
2*70 | 23.1 | 1601 | 773 | 26.5 | 1868 | 1040 |
2*95 | 26.8 | 2173 | 1024 | 31.4 | 2771 | 1623 |
2*120 | 29.0 | 2667 | 1217 | 33.7 | 3320 | 1869 |
2*150 | 32.4 | 3319 | 1533 | 37.2 | 4054 | 2268 |
2*185 | 35.7 | 4100 | 1867 | 40.7 | 4917 | 2684 |
表25 0.6/1kV聚氯丁二烯隔绝铜带拦截通信电缆通信电缆
Table25 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称受力 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算的外径 Calculated external diameter (mm) | 求算权重 Calculated weight (kg/km) | 计算方法外径 Calculated external diameter (mm) | 测算总重量 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
3*1.5 | - | - | - | - | - | - |
3*2.5 | 11.4 | 205 | 159 | 14.6 | 339 | 292 |
3*4 | 13.3 | 283 | 208 | 16.5 | 436 | 361 |
3*6 | 14.4 | 363 | 251 | 17.6 | 528 | 416 |
3*10 | 17.1 | 540 | 356 | 20.3 | 733 | 549 |
3*16 | 19.5 | 724 | 439 | 22.7 | 943 | 657 |
3*25 | 23.0 | 1074 | 618 | 26.2 | 1331 | 874 |
3*35 | 24.4 | 1363 | 730 | 27.6 | 1634 | 1001 |
3*50 | 24.9 | 1726 | 867 | 28.3 | 2013 | 1155 |
3*70 | 27.8 | 2351 | 1110 | 31.2 | 2669 | 1428 |
3*95 | 32.3 | 3242 | 1519 | 37.0 | 3965 | 2242 |
3*120 | 35.3 | 3985 | 1809 | 40.1 | 4781 | 2605 |
3*150 | 38.7 | 4876 | 2197 | 43.7 | 5759 | 3080 |
3*185 | 42.8 | 6038 | 2689 | 48.0 | 7021 | 3672 |
3*240 | 48.1 | 7817 | 3411 | 53.4 | 8937 | 4532 |
3*300 | 53.3 | 9695 | 4168 | 58.9 | 10955 | 5428 |
表26 0.6/1kV聚氯氯乙烯隔绝铜带闭屏供电线缆
Table26 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称剖面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
折算外径 Calculated external diameter (mm) | 计算方式总重量 Calculated weight (kg/km) | 确定外径 Calculated external diameter (mm) | 计算容量 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
4*1.5 | - | - | - | - | - | - |
4*2.5 | 12.3 | 252 | 189 | 15.5 | 395 | 332 |
4*4 | 14.4 | 351 | 251 | 17.6 | 516 | 416 |
4*6 | 15.6 | 458 | 307 | 18.8 | 636 | 485 |
4*10 | 18.6 | 663 | 417 | 21.8 | 872 | 627 |
4*16 | 21.3 | 930 | 549 | 24.5 | 1168 | 787 |
4*25 | 25.3 | 1388 | 779 | 28.5 | 1667 | 1058 |
4*35 | 26.8 | 1769 | 925 | 30.2 | 2077 | 1233 |
4*50 | 28.0 | 2261 | 1116 | 31.3 | 2581 | 1436 |
4*70 | 31.7 | 3140 | 1484 | 36.3 | 3846 | 2190 |
4*95 | 36.0 | 4253 | 1957 | 38.3 | 4834 | 2537 |
4*120 | 38.6 | 5225 | 2325 | 43.6 | 6106 | 3205 |
5*150 | 42.9 | 6411 | 2839 | 48.1 | 7401 | 3829 |
4*185 | 48.5 | 7965 | 3499 | 53.9 | 9093 | 4627 |
4*240 | 53.6 | 10307 | 4433 | 59.2 | 11575 | 5701 |
4*300 | 59.3 | 12829 | 5459 | 65.1 | 14254 | 6885 |
表27 0.6/1kV聚氯乙稀耐压铜带手机屏蔽电能线缆
Table27 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称受力 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算外径 Calculated external diameter (mm) | 求算权重 Calculated weight (kg/km) | 算出外径 Calculated external diameter (mm) | 确定体积 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
5*1.5 | 12.2 | 233 | 186 | 15.4 | 375 | 328 |
5*2.5 | 13.3 | 298 | 219 | 16.5 | 451 | 372 |
5*4 | 15.6 | 419 | 293 | 18.8 | 596 | 471 |
5*6 | 17.0 | 549 | 361 | 20.2 | 742 | 554 |
5*10 | 20.3 | 773 | 487 | 23.5 | 1001 | 715 |
5*16 | 23.3 | 1075 | 621 | 26.5 | 1335 | 880 |
5*25 | 27.8 | 1602 | 874 | 31.3 | 1934 | 1206 |
5*35 | 29.9 | 2134 | 1112 | 33.3 | 2484 | 1461 |
表28 0.6/1kV聚氯丁二烯绝缘层铜带关闭电能电缆电线
Table28 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称横截面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算方式外径 Calculated external diameter (mm) | 核算称重 Calculated weight (kg/km) | 核算外径 Calculated external diameter (mm) | 折算含水量 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
3*4+1*2.5 | 13.9 | 326 | 235 | 16.5 | 477 | 386 |
3*6+1*4 | 15.3 | 433 | 296 | 18.0 | 599 | 462 |
3*10+1*6 | 17.8 | 614 | 392 | 20.5 | 807 | 585 |
3+16+1*10 | 20.6 | 868 | 521 | 23.2 | 1090 | 743 |
3*25+1*16 | 24.3 | 1280 | 729 | 26.9 | 1541 | 990 |
3*35+1*16 | 25.4 | 1566 | 838 | 28.1 | 1842 | 1115 |
3*50+1*25 | 25.6 | 2015 | 1005 | 28.4 | 2300 | 1290 |
3*70+1*35 | 28.1 | 2728 | 1276 | 30.9 | 3040 | 1588 |
3*95+1*50 | 33.7 | 3757 | 1749 | 37.7 | 4466 | 2458 |
3*120+1*70 | 36.0 | 4697 | 2109 | 40.0 | 5475 | 2887 |
3*150+1*70 | 40.2 | 5599 | 2507 | 44.2 | 6465 | 3374 |
3*185+1*195 | 44.3 | 7016 | 3095 | 48.7 | 8007 | 4086 |
3*240+1*120 | 49.5 | 9031 | 3903 | 53.9 | 10133 | 5005 |
3*300+1*150 | 55.5 | 11185 | 4768 | 59.9 | 12417 | 6000 |
表29 0.6/1Kv 聚氯氯乙烯绝缘层铜带屏弊电力网通信电缆
Table29 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称剖面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
求算外径 Calculated external diameter (mm) | 核算总重 Calculated weight (kg/km) | 算起外径 Calculated external diameter (mm) | 计算出来含水量 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
4*4+1*2.5 | 15.1 | 394 | 278 | 18.3 | 567 | 444 |
4*6+1*4 | 16.7 | 525 | 350 | 19.9 | 715 | 529 |
4*10+1*6 | 19.7 | 746 | 463 | 22.9 | 967 | 668 |
4+16+1*10 | 22.7 | 1036 | 594 | 25.9 | 1289 | 820 |
4*25+1*16 | 26.8 | 1525 | 822 | 30.2 | 1834 | 1089 |
4*35+1*16 | 28.4 | 1915 | 976 | 31.7 | 2240 | 1260 |
4*50+1*25 | 31.9 | 2631 | 1335 | 35.3 | 2994 | 1631 |
4*70+1*35 | 35.6 | 3566 | 1700 | 40.4 | 4364 | 2406 |
4*95+1*50 | 41.2 | 4828 | 2246 | 46.1 | 5762 | 3056 |
4*120+1*70 | 45.3 | 6020 | 2708 | 50.4 | 7054 | 3562 |
4*150+1*70 | 49.5 | 7208 | 3224 | 54.7 | 8349 | 4185 |
4*185+1*195 | 55.0 | 9023 | 3985 | 60.5 | 10311 | 5023 |
4*240+1*120 | 61.8 | 11640 | 5044 | 67.5 | 13111 | 6200 |
4*300+1*150 | 68.3 | 14410 | 6151 | 74.3 | 16064 | 7418 |
表30 0.6/1kV聚氯丁二烯接地铜带手机屏蔽电力网缆线
Table30 PVC insulated copper tape screen power cables with rated voltages 0.6/1kV芯数及标称断面 Number of cores and Nominal cross area (mm2) | 无铠装Unarmored | 铠装Armored | ||||
计算方式外径 Calculated external diameter (mm) | 来计算体积 Calculated weight (kg/km) | 计算方式外径 Calculated external diameter (mm) | 来计算含水量 Calculated weight (kg/km) | |||
VVP2 | VLVP2 | VVP2-22 | VLVP2-22 | |||
3*4+2*2.5 | 14.7 | 370 | 264 | 17.9 | 538 | 432 |
3*6+2*4 | 16.4 | 502 | 339 | 19.6 | 689 | 526 |
3*10+2*6 | 19.0 | 699 | 440 | 22.2 | 913 | 654 |
3+16+2*10 | 22.1 | 975 | 567 | 25.3 | 1222 | 814 |
3*25+2*16 | 26.0 | 1426 | 779 | 29.2 | 1715 | 1068 |
3*35+2*16 | 27.0 | 1709 | 935 | 30.4 | 2020 | 1246 |
3*50+2*25 | 29.6 | 2373 | 1261 | 33.0 | 2710 | 1599 |
3*70+2*35 | 33.0 | 3198 | 1534 | 37.7 | 3934 | 2271 |
3*95+2*50 | 38.6 | 4045 | 2050 | 43.4 | 4916 | 2921 |
3*120+2*70 | 42.2 | 5475 | 2471 | 47.3 | 6438 | 3435 |
3*150+2*70 | 44.9 | 6357 | 2850 | 50.0 | 7385 | 3878 |
3*185+2*195 | 50.4 | 8064 | 3566 | 55.8 | 9236 | 4738 |
3*240+2*120 | 58.1 | 10369 | 4513 | 63.7 | 11740 | 5884 |
3*300+2*150 | 62.8 | 12780 | 5467 | 68.6 | 14284 | 6971 |
♔注:表15~表30中提高的数据线成分尽寸均为标称尽寸,仅用来参考使用。现实的生产方式的时候会有很大定的差别,比如装配126邮件要求更精确性尽寸,应提起与产生方联系起来。
Note : The dimensions offered in table 15-30 are nominal dimensions which are only for reference only. It will produce error in actual installtion. If you want exact dimensions, please contact with the manufacturer.